Rack Mounted PDU's top of page
By
Leo P. Soucy, P.E
Initially, power for computer equipment in a rack was provided via “power strips”. These were usually 15 or 20 amp rated units with multiple receptacles for plugging in the computer equipment. As rack loads increased these “power strips” could not support the higher loads so rack mounted “power distribution units” (PDUs) were developed. Depending on the manufacturer and optional features, PDUs included metering, remote monitoring and in some case remote control and load monitoring of each receptacle. To support the high loads in the cabinets these PDUs were designed for higher current and multiple phases. The National Electrical Code (NEC) has a provision that 15 and 20 amp receptacles must be protected by a 20 amp maximum circuit protective device – circuit breaker. As the PDU designs proliferated, this NEC requirement resulted in many different circuit protection configurations for the groups of receptacles of a PDU assembly.
FEA has examined a number PDUs to determine how they were configured, their physical construction and to develop any application constraints. These inspections were at the request of one client that was concerned with the proliferation of “rack mounted PDUs” that were being advocated by computer server manufacturers, cabinet manufacturers and “rack mounted PDU” manufacturers. There are now dozens of units comprising multiple voltage, phases and current configurations. With dual power corded equipment it is imperative that you thoroughly understand the specific “rack mounted PDU’s” rating and metering. Below are a few examples of “rack mounted PDU’s” that we have examined.
All “rack mounted PDUs” were to be applied in cabinets that housed dual power cord computer equipment so this was the basis of the analysis. The analysis evaluated the overall PDU assembly rating and the ratings of groups of plugs protected by the 15 or 20 amp circuit breakers internal to the PDU. It is important to note that dual power cord equipment MUST be plugged into the exact same receptacle in both “rack mounted PDUs” otherwise it is impossible to insure that the branch circuit, circuit breaker will not be overloaded should one PDU fail. All the PDU’s will be applied on a 208 volt single or three phase system so all calculations are based on this utilization voltage.
Unit 1 Analysis
30A, 250v Single Phase – with branch circuit protection, receptacles and ammeters
This PDU includes a 30A 250V NEMA single phase twist-lock plug. Internal to the PDU this is further sub-divided into two 15A 2P branch circuits protected by circuit breakers. Each circuit breaker has an ammeter and feeds a group of receptacles.
Analysis of the PDU per the NEC requirement determined the following:
- PDU assembly NEC rating – 24 amps @ 208 volts single phase – 5 kW.
- Internal 15A branch circuit NEC rating – 12 amps @ 208 volts – 2.5 kW
- PDU assembly rating equals PDU internal rating – 5.0 kW
Due to the potential load transfer of the dual power cord equipment the maximum load on a PDU branch should not exceed 2.5 kW so it is recommended that each ammeter be labeled:
DO NOT EXCEED
6 AMPS
Unit 2 Analysis
30A 250v Three Phase – with branch circuit protection, receptacles and ammeters
The PDU includes a 30A 250V NEMA three phase twist-lock plug. Internal to the PDU this is further sub-divided into three 20A 2P branch circuits protected by circuit breakers. Each circuit breaker has an ammeter and feeds a group of receptacles.
Analysis of the PDU per the NEC requirements resulted in the following:
- PDU assembly NEC rating – 24 amps @ 208 volts three phase – 8.7 kW.
- Internal 20A branch circuit NEC rating – 16 amps @ 208 volts single phase – 3.3 kW
- The combined NEC rating of the three internal branch circuits is 9.9 kW which is greater than the PDU assembly rating of 8.7 kW so the assembly rating is the limiting factor.
The maximum load on each internal branch circuit (group of receptacles) should not exceed 2.9 kW. Since the PDU is feeding dual power cord equipment the load needs to be no greater than 50% of its rating so it is recommended that each ammeter be labeled:
DO NOT EXCEED
7 AMPS
Unit 3 Analysis
30A, 250v Single Phase Tandem PDU – with branch circuit protection, receptacles and ammeters
Two identical 30A 250V single phase PDUs are housed in the same PDU enclosure. One will be called “A” and the other “B”. There is no physical separation between the “A” and “B” sections.
The PDU includes two 30A 250V NEMA single phase twist-lock plug – one of the “A” circuit and one for the “B” circuit. Each 30a circuit feeds two internal 20A 2P branch circuits protected by circuit breakers. Each circuit breaker has an ammeter and feeds a group of receptacles.
The following NEC analysis is for each PDU plug:
- PDU assembly NEC rating – 24 amps @ 208 volts single phase – 5.0 kW per plug
- Internal branch circuit NEC rating – 16 amps @ 208 volts single phase – 3.3 kW
- The combined NEC rating of the two internal branch circuits is 6.6 kW which is greater than the PDU assembly rating of 5.0 kW so the unit rating is limited to 5.0 kW.
The maximum load on each internal branch circuit (group of receptacles) should not exceed 2.5 kW. Since the PDU is feeding dual power cord equipment the load needs to be no greater than 50% of its rating so it is recommended that each ammeter be labeled:
DO NOT EXCEED
6 AMPS
This PDU was not recommended for the following reasons:
- Both the “A” and “B” sources are housed in a common enclosure with no physical separation, although this PDU could be used as a 10kW “A” source only PDU.
- The assembly consists of large solder connections which are not deemed reliable enough for mission critical application.
- The ammeter monitors the combined total amps of the two circuit breakers on either the “A” side or “B” side and as such there is no way of knowing if the individual 20 amp breakers are overloaded.
- The ground wire is terminated to the PDU enclosure with the ground pin of the receptacles also terminated to the PDU enclosure. There is no direct connection of the receptacle ground pin to the cord ground connector.
Conclusion
In all cases the rating of PDU’s 1, 2 and 3 is the NEC rating of the PDU’s NEMA plug. Only PDU 1 has the capacity to allow the branch circuits to be loaded to their NEC rating. Loading PDU 2 and 3 branch circuits to their NEC rating will result in tripping the 30 A breaker feeding the PDU even though the PDU branch circuit breakers will not be overloaded. It is important to understand what amperage the PDU meter is measuring and adjust your load thresholds accordingly. As we found with Unit 3 the meter would not provide accurate information to help guard against a internal branch circuit overload condition.
Unit 3, on physical inspection, had numerous problems with the configuration, grounding and general workmanship. Obviously this was being heralded as a cost effective solution to purchasing two “rack mounted PDU’s” for each cabinet or a means to achieve a 10kW PDU. Care should be given to proper PDU selection and application and the same analysis can be applied to the larger 50 or 60A PDUs since they need to further subdivide into smaller 20A branch circuits feeding groups of receptacles.
top of page |